During
the last State of Illinois Elevator Safety Board meeting we received clarification
on what buildings need to do if they introduce sprinklers into elevator machine
areas or hoistways. If a building has
install sprinklers in existing elevator machine area or hoistway they must
install a shunt trip as well as have Fireman’s Phase I & II with alternate
landing recall. Recently the IDPH
required all nursing homes, extended care facilities, etc to be sprinkled as
this is the best way to add fire safety to buildings. The issue came about with some older
buildings that have older elevator equipment that where not capable of fireman’s
recall.
ASME
17.3 includes a note that indicates[17.3 is the code for existing elevator systems]
“The
installation of sprinklers in an existing machine room or hoistway is an
alteration. See SME A17.1, requirements 8.7.2.8
and 8.7.3.8”
The
intention behind this note is if you have a building that is on fire and the
shunt trip removes power from the elevator system after a heat detector goes
off[the heat detector should go off before the sprinklers], the elevator will
stop, the elevator could get stuck between floors and if there are people in
the elevator they may be stuck and exposed to smoke inhalation. Now that all elevators in the State of
Illinois have door restrictors on the elevators you are trapped in the
elevator. If fire recall was installed on the elevator, fire recall would bring
the elevator down before the heat would go off, a smoke detector would
typically go off before a heat detector, the elevator would go to the
designated landing and the doors would open and the elevator would be out of
service until reset by emergency services or the elevator company.
We
have a lot of older buildings in Illinois with older elevator equipment. If the building is installing sprinklers
they can either choose not to sprinkle the elevator machine area and hoist way
or the elevator needs to be equipped with Fireman’s recall. For some older buildings it may require replacement
of the elevator control system.
If
you have an questions or would like information from Colley Elevator you can go
to www.colleyelevator.com, email Craigz@colleyelevator.com or call
630-766-7230.
Thanks to Chicago Elevator Maintenance for sharing this valuable information about "Introduction of sprinklers into existing elevator machine rooms or hoist ways"!
ReplyDeleteMake Elevating your lifestyle!
Elevator company Dhaka
Elevator company Bangladesh