We have been getting more and more questions about
FEO[Firefighters emergency operation]. I
wanted to put a better posting together to show the different items that
encompass FEO. For this purpose it is to
explain what fire equipment is needed for modernization of a control system.
Definitions
Fireman’s service
phase I – This is the key switch on the main floor that will
recall the elevator to the floor. The
intention is to bring the elevator to the main landing to give access to the
elevator to emergency personnel. This
key switch is provided by the elevator contractor during a modernization.
Fireman’s service
phase II – This is the key switch in the elevator that when
initiated will allow emergency personnel to use the elevator. All hall calls are disabled, the elevator can
only be operated from the car station inside the elevator.
Automatic recall – This is when the
elevator is hooked to smoke detectors.
When a fire detector goes off the elevator will “recall” to the
appropriate floor. I.E. if the main
lobby fire recall detector goes off the elevator will “recall” away from the
main lobby floor and stay there with the doors open, no one can call or use the
elevator[with exception of emergency personnel]. If a fire recall detector goes off on the 7th
floor the elevator would “recall” to the main landing and stay there with the
doors open, no one can call or use the elevator.
What fire equipment
does the fire control company need?
1.
Fire recall detector at each landing
2.
Fire recall detector in the machine
room
3.
Relays in the elevator machine room
4.
Annunciator somewhere in the
building[look for direction from the fire panel company]
5.
If you have sprinklers in the machine
room you will need a heat detector and shunt trip
6.
If you have sprinklers in the
hoistway you will need a heat detector, if you have a heat detector you need a
smoke detector. If you have a heat
detector you will need a shunt trip.
[Fire detector outside of each hoist way entrance]
[Phase I key switch in hall way - This is a City of Chicago location in door frame]
[Phase II operation with closed door]
[Phase II operation with open door showing fire controls]
[Fire relays in machine room - Provided by fire control panel company]
[On left fire control panel provided by fire control panel company]
*In the City of Chicago, it has been permitted in the past
to be hooked to sprinkler flow switches.
Guidance form AHJ[Authority
Having Jurisdiction] – If you live in AHJ that is open to
giving direction I would recommend having your fire panel company get
information on what they need to do from them. At
times the AHJ will require additional work, strobes and pull stations. Any additional scope of work is up to the AHJ’s
Fire Prevention Bureau as they have authority on this item. Get the AHJ’s requirements in writing! You don’t want any surprises after you start
the elevator project because a new Fire Chief starts and doesn’t know the
conversation you had with the previous Fire Chief.
As
always feel free to contact us at www.colleyelevator.com, email Craigz@colleyelevator.com or call
630-766-7230.
Thanks to Chicago Elevator Maintenance for sharing this information about "Elevator Fireman’s automatic recall and Fireman’s service Phase I & II [FEO]"!
ReplyDeleteMake Elevating your lifestyle! Photos are really attractive!
Elevator company Dhaka
Elevator company Bangladesh
Websites for Elevator Contractors
ReplyDeleteWe are the top rated web design company that build professional contractor websites for Drywall, Elevator, Elevator, Fencing, Insulation and Paving at the most reasonable prices.
For More Info :- https://contractorwebsites.com/
Get all the benefits such as lower costs, flexibility, portability and most importantly you fully own your website. We offer robust website maintenance packages for your peace-of-mind.
ReplyDeleteElevator Contractor Website Design | Moving Walkways Website Design