Aluminum wiring - Elevators

I was at a few buildings this week where I saw aluminum wiring.  For those who are not familiar with why we in the elevator business [or any electrical related field] cringe when we see aluminum wiring is because it causes a lot of problems.   Many times we address the symptom of the "electrical issues", not the cause[which can be the aluminum wire].

Case - We had a building where the elevator kept setting the motor starter overloads, typically this is from over current on the motor which identifies a malfunction somewhere or a low voltage issue from the building power.  We worked on this problem for over a week on and off and building was very frustrated.  We looked further into the electrical and found there was a loose connection/melted connection on the vault that was causing more issues then just the elevator problems.  The elevator mechanic's trouble shooting typically stops at the disconnect, in this particular situation the mechanic went further and discovered the root problem which was a bad connection on a lug in the electrical room.  It was an expensive resolution for the building but it saved the building from a fire and future electrical issues due to the bad connection points from the aluminum wiring.

Aluminum wiring got to be popular in the mid 1960’s when the price for copper increased.   This is also the time where there was a building explosion in the Chicago land area.  How does this affect your elevators?  It can lead to motor burn out, starter malfunction and general reliability issues.  And it is difficult to find because the aluminum wiring issue may be in the elevator disconnect, electrical breaker where the elevator disconnect gets power, vault termination or anywhere in between there is a connection point.


[This is a picture of the main line disconnect the aluminum wire is coming in from the top which is feeding power from the building feed to the disconnect and copper wire is on the bottom feeding the elevator motor starter]


[This is a closer picture of the connection points on the disconnect - you can see the color difference between the wires, top wires are aluminum and the bottom right connection shows the copper wire]
  
Aluminum oxidation

Most metals (with a few exceptions, such as gold) oxidize freely when exposed to air. Aluminum oxide is not an electrical conductor, but rather an electrical insulator. Consequently, the flow of electrons through the oxide layer can be greatly impeded. However, since the oxide layer is only a few nanometers thick, the added resistance is not noticeable under most conditions. When aluminum wire is terminated properly, the mechanical connection breaks the thin, brittle layer of oxide to form an excellent electrical connection. Unless this connection is loosened, there is no way for oxygen to penetrate the connection point to form further oxide.

[oxidation]

Coefficient of expansion and creep

Aluminum wire used before the mid-1970s has a coefficient of expansion that varies significantly from the metals common in devices, outlets, switches, and screws. Many terminations of aluminum wire installed in the 1960s and 1970s continue to operate with no problems. However, problems can develop in the future and some connections were not made properly when installed, including not wrapping wires around terminal screws and inadequate torque on the connection screws. There can also be problems with connections made with too much torque as it causes damage to the wire.

Aluminum and steel both expand and contract at different rates under thermal load, so a connection can become loose, and loose connections get progressively worse over time. This cycle results in the connection loosening slightly, overheating, and allowing intermetallic steel/aluminum alloying to occur between the conductor and the screw terminal. This results in a high-resistance junction, leading to additional overheating. Although many believe that oxidation was the issue, studies have shown that oxidation was not significant in these cases. The problems related to aluminum wire are typically associated with older pre-1970s solid wire smaller than No. 8 AWG, as the properties of that wire result in significantly more expansion and contraction than modern day AA-8000 series aluminum wire. Older solid aluminum wire also had problems with a property called creep, which made the wire permanently deform or relax over time under load.

[What can happen with creep]

Joining aluminum and copper wires


Another issue is the joining of aluminum wire to copper wire. As aluminum and copper are dissimilar metals, galvanic corrosion can occur in the presence of an electrolyte and these connections can become unstable over time.

Tin coated copper wire 

There is also tin coated copper wire which can be confused with aluminum wire which is similar in color to aluminum wire.  I was recently corrected by an electrician when we where reviewing the electrical wiring at a school.

The point is that if you have aluminum wire, you should remove it.  If you choose to keep it you will need an electrician to tighten connections and maintain the wiring to prevent shorts, fires and unreliable electrical connectivity on regular intervals.  

If you have an questions or would like information from Colley Elevator you can go to www.colleyelevator.com, email Craigz@colleyelevator.com or call 630-766-7230.


9 comments:

  1. I just want to let you know that I just check out your site and I find it very interesting and informative..
    Aluminum

    ReplyDelete
  2. All the contents you mentioned in post is too good and can be very useful. I will keep it in mind, thanks for sharing the information keep updating, looking forward for more posts.Thanks
    אלומיניום

    ReplyDelete
  3. Thanks to Chicago Elevator Maintenance for sharing this valuable information about "Aluminum wiring - Elevators"!
    Make Elevating your lifestyle!
    Elevator company Dhaka
    Elevator company Bangladesh

    ReplyDelete
  4. Been in the electrical field for 22 years, wired everything there is to be wired, Aluminum is the back bone of every electrical grid, I grow tired of un-informed scare mongers about aluminum wire. 1st off, the materials used are different, 2nd off the "bad aluminium" is on branch wire devices, 3rd off there are thousands of houses wired with this aluminium where I live and have not had any calls I can remember to fix a bad connection, but I can remember hundred of bad connections that involved copper branch wiring. It comes down to this, the material is not to blame for poor workmanship at time of installation. Furthermore the disconnect in the picture is by my guess very very old, has anyone ever gon back and retorqued the connections during their maintenance cycles? so blame the conductor for lack of diligence on the maintenance?
    All electrical connections should be checked, but they never are and yet some of them are approaching 100 years old and anyone is surprised when a 30 to 50 year old connection needs attention?! Properly installed Aluminium conductors are in every way equal to copper.

    ReplyDelete
  5. More information about view here :https://www.techdoct.com/electrical/what-is-meant-by-cable-practically-difference-between-copper-and-aluminium-cables-how-to-avoid-cable-failure/?preview_id=67&preview_nonce=ee8fada114&post_format=standard&_thumbnail_id=1579&preview=true

    ReplyDelete
  6. When it comes to elevators and aluminum wiring, safety and reliability are paramount. For top-quality Aluminum THHN-THWN building wire solutions in the Philippines, look no further than AM Wire. Their expertise in providing durable and efficient wiring options is unmatched. Learn more about their offerings at Aluminum THHN-THWN building wire Philippines. Elevate your projects with their trusted solutions.

    ReplyDelete
  7. The Origins of Aluminum:
    Let's unravel the history and discovery of aluminum, from its early isolation to becoming a staple in various industries.aluminum

    ReplyDelete
  8. This comment has been removed by the author.

    ReplyDelete
  9. 4 Gauge Copper Lugs are made from 99.9% pure annealed copper, providing a high degree of conductivity for maximum current flow. This particular variant comes with a wider pad offering a larger clamping surface and is suitable for use with 4 Gauge Battery Cable & 3/8" (M10) Stud.

    ReplyDelete