note that in the State of Illinois every elevator’s pit ladder must comply with
the current code requirements by 1/1/15.
Every elevator must #1, have an elevator pit ladder and it will need to
meet all of the requirements spelled out in the code. Many pit ladders that are existing do not
meet the new requirements which include being 4 ½” from the pit wall to the
center rung of the ladder, rough surface on the rungs to prevent slipping and
coming up to 48” above the 1st landing and not further than 39” away
from the unlocking device. Please find
other OSHA rules below
What
this all means for building owners is that they need to review their current
pit ladder to see if it is within the range of the code. Many building owners have put a aluminum ladder
in the pit instead of a proper pit ladder made for elevator pits, these most
likely will not meet the code requirements. Ask your elevator company or elevator inspector to walk you through
the requirements.