We
recently had code training and one of the items that I tend to get a lot of
questions on by our field teams, electricians and fire companies are smoke
detectors, sprinklers, heat detectors and shunt trips.
For
all the items listed below please consult AHJ for specific rules to the area
you are working in and items the AHJ may have taken exception to national/local
codes.
Smoke detectors
Smoke
detectors on ceilings must be at least 4 inches from the wall.
Smoke
detector on walls must be between 4 inches and 12 inches from the ceiling.
Smoke
detectors are required in machine rooms.
Smoke
detectors are required at the top of the hoist way when either a sprinkler is
present or the passenger cab is not a fire-rated design.
No
smoke detectors shall be provided in the elevator pits per NFPA 72.
Smoke
detector may also be provided to operate hoist way smoke evacuation equipment,
but it cannot be connected to the elevator system.
Sprinklers - Sprinklers may be
located in the following elevator equipment areas:
•
Machine Room
•
Top of Hoistway – Sprinklers are not required
when the passenger elevator cab is a fire rated design.
•
Pit – Sprinklers located within 24” of the
pit floor do not require a heat sensor for shunt trip disconnects nor a smoke
sensor.
[Sprinkler, heat & smoke]
Heat detectors - Heat detectors are required within 2 feet of each sprinkler head in elevator equipment areas and pit. Exception in pit when the sprinkler is within 24” of the pit floor.
Shunt Trip disconnect
system
Shunt
trip disconnect is required on any new or existing elevator where a sprinkler
is located at the top of the hoistway or in the machine room.
A
properly located sprinkler in the pit only, will not cause shunt trip
disconnect to be required.
Non-sprinklered
elevators will not have a shunt trip disconnect system.
Operation
of the shunt trip disconnect must cause disconnection of normal power and
emergency/stand-by power.
Operation
of the shunt trip disconnect must also cause disconnection of any internal
auxiliary power operations, such as battery lowering devices on hydraulic
elevators or anti-entrapment (TAP) devices on traction elevators if so
equipped. The shunt trip disconnect must
have a set of contacts that signal the control system to prevent movement of
the elevator.
Location
of the shunt trip disconnect is not specified by code. Shunt trip disconnect can be in a fire
command center, elevator machine room, electrical room, or other location. If in the machine room, it may be combined
with the main disconnect.
Power
to and operation of the shunt trip shall be independent of the elevator control
and shall not be self-resetting.
[Shunt & disconnect seperate]
[Shunt/disconnect combination unit]
Reference - Joseph P. Donnelly, PE Elevator Education Program 2019
If
you have any questions or would like additional information feel free to
contact me at CraigZ@colleyelevator.com or
630-766-7230 ext. 107.
Also
check us out on Instagram @Colleyelevator see what we have been up to.
No comments:
Post a Comment